Suitable for air-cooling system, max 1500V and 250A continuous working current
PDU-E10-C250-33F | PDU-E10-B400 | PDU-E15-C250-33F | PDU-E15-B400 | PDU-E15-C250-33W | PDU-E15-C350-1310 | |
Nominal working voltage | 1000V | 1000V | 1500V | 1500V | 1500V | 1500V |
Nominal working current | 250A | 400A | 250A | 400A | 250A | 350A |
System type | Air-cooling | Liquid-cooling | ||||
MCCB | 250A/DC1000V | 400A/DC1000V | 250A/DC1500V | 400A/DC1500V | 250A/DC1500V | 400A/DC1500V |
DC contactor | 250A/DC1500V | 400A/DC1000V | 250A/DC1500V | 400A/DC1500V | 250A/DC1500V | 500A/DC1500V |
Shunt | 300A/0.2% | 500A/±0.2% | 300A/0.2% | 500A/±0.2% | 300A/0.2% | ±500A |
Fuse | 315A/DC1000V | 450A/DC1000V | 315A/DC1500V | 450A/DC1500V | 315A/DC1500V | 450A/DC1500V |
Altitude | ≤2000m (above 2000m reduce capacity) | |||||
Environment | -25℃~85℃ | |||||
Humidity | ≤90% no condense | |||||
IP level | IP20 | IP65 | ||||
Size | 648*420*222.5mm | 648*420*255mm | 760*582*160mm | 760*582*150mm | ||
Weight | ≤25kg | ≤40kg |